From the plan to the finished project
Step 11 – Installing the cornice lighting
After completing the cornice, I decided fairly spontaneously to highlight it with lighting. A low-priced LED profile, aluminium profile S with an opal cover, is fitted directly behind the cornice over a length of 5 metres. Since it is not visible, its role is to provide cooling and protection from dust and mechanical damage. There are two sections of two metres and one section of one metre. Using 3 profiles instead of one has practical advantages: it reduces shipping costs, as lengths over two metres are classed as bulky goods, and makes handling easier. The lighting again uses a type 3528-300 LED strip in 24 V, warm white, rated at 4.8 watts per metre. The strip is installed as a complete 5-metre length. At the end of this 5-metre strip, after a cable run of about 10 metres using a 2.5 mm² supply cable, I measured 22.8 V. The voltage drop is therefore 6%. In the application shown here, this is not noticeable to the naked eye as a reduction in brightness. The cornice lighting is also too bright when undimmed. LED strips can be connected at both ends to compensate for voltage losses along longer strips. This was not necessary with the Neonica strips used here, whose copper tracks appear to be adequately sized. Cheap products may use tracks made from other materials.